3/4" NPT, 120 VAC 50/60 Hz, 125 VA Pilot Duty, 7.5 A FLA, 15 PSI Steam/160 PSI Water, Self-Cleaning Probe, Low Water Cut-Off for Hot Water and Steam Boiler
Product Description
More Information
Green LED Indicating Power is On
• Red LED Indicating Low Water Condition
• Test Button
• Self Cleaning Probe
• no Lock Out with Loss of Power if Probe is in Water""
• Boiler Control Low Water Cut-Off • Item Low Water Cut-Off • Type Self-Cleaning Probe • Used On Item Steam and Hot Water Boiler • Applicable Standard UL (Canada and US), ASME • Voltage Rating 120 Volt at 50/60 Hertz • Power Rating 125 Volt Amp at 120 Volt AC 50/60 Hertz (Pilot Duty) • Current Rating 7.5 Amp at 120 Volt AC • Pressure Rating 15 PSI (Steam), 160 PSI (Water) • Temperature Rating 250 Deg F (Water) • Probe Sensitivity 20000 Ohm • Electrical Enclosure Rating NEMA 1 • Humidity 85 Percent (Non-Condensing) • Power Rating 3 Volt Amp • Application Commercial, Industrial • Includes U Barrel Probe
• Voltage Rating 120 Volt at 50/60 Hertz • Power Rating 125 Volt Amp at 120 Volt AC 50/60 Hertz (Pilot Duty) • Current Rating 7.5 Amp at 120 Volt AC • Pressure Rating 15 PSI (Steam), 160 PSI (Water) • Temperature Rating 250 Deg F (Water) • Probe Sensitivity 20000 Ohm • Electrical Enclosure Rating NEMA 1 • Humidity 85 Percent (Non-Condensing) • Power Rating 3 Volt Amp • Application Commercial, Industrial • Includes U Barrel Probe
• The Series 751P/752P probe type LWCOs provide protection against low water conditions for commercial and industrial applications. These controls are fully CSD-1 compliant and are primarily used as LWCOs on hot water heating boilers.